Our expertise put to work on a complex smoke ventilation upgrade project

Our expertise put to work on a complex smoke ventilation upgrade project
The video only loads when you click play.

At its industrial site in Bascharage, Luxembourg, Tontarelli needed to upgrade a significant part of its natural smoke ventilation system. The project involved three industrial halls, with several dozen opening vents and different technical requirements in each area. The challenge was to find a reliable solution suited to the existing installation, while respecting the client’s technical and budgetary constraints

Screenshot

Finding a solution suited to the existing installation

When renovating, it is not always necessary to replace an entire system. Our design office therefore assessed the existing equipment to define the most suitable solution for each hall.

In Hall 1, four faulty drives were replaced with D+H ZA series motors, and the old smoke ventilation control panel was replaced with a new D+H RZN control panel.

In Hall 2, ten drives were malfunctioning. Motors from Hall 3 that were still working and the same type as those already installed could be reused. This solution also made it possible to keep the existing smoke ventilation control panel.

Finally, the drive system in Hall 3 was fully renovated, with 32 new D+H ZA series motors installed.

This approach made it possible to balance modernisation, technical constraints and budget control.

See images of the natural smoke ventilation system upgrade at the Tontarelli site in Bascharage and the work carried out by our teams.

Screenshot
Screenshot

From design office to site

The success of a modernisation project depends on more than the solution defined on paper. It also depends on how it is implemented on site. Our technicians had to adapt to the site layout and work mainly from the roof to access the various opening vents. The work included:

  • Removing the frames from the opening vents
  • Removing the motors 
  • Installing D+H motors or the existing motors
  • Refitting the frames to the opening vents
  • Installing and commissioning the smoke ventilation control panel

Overall, the work took nearly a month for a team of two technicians.

Thanks to their experience, organisation and strong on-site performance, our technicians also managed to complete the entire project within the timeframe requested by the client.

Expertise tailored to the client’s constraints

This project is a perfect example of how we support our clients with existing installations.

When the solution is not obvious, our first role is to understand the client’s requirements, then devise a response that is technically feasible and economically viable. The design office defines the solution. Our technicians then put it into practice in the building, taking account of the realities on site.

From design to delivery, our goal remains the same: to offer the client the solution best suited to their installation and their

“D+H was able to meet our needs” Client testimonial in the project video

Screenshot

Do you need to bring your smoke ventilation system into compliance?

Please contact D+H

Een zakelijke vraag aan D+H BeLux? Get in touch

Full transcript

00:00:10:04 – 00:00:11:02

Following the latest

00:00:11:02 – 00:00:17:02

periodic inspection, we were given a deadline to bring our systems into compliance

with smoke ventilation requirements.

00:00:17:06 – 00:00:19:02

In our oldest halls.

00:00:19:02 – 00:00:25:06

We contacted our usual maintenance provider,

but they were unable to meet our needs.

00:00:25:10 – 00:00:36:10

D+H was able to meet our needs, namely to refurbish one hall

and reuse the existing functional equipment to bring

00:00:36:10 – 00:00:43:38

two other halls into compliance, all within six months

from the design stage to project completion.

00:00:47:36 – 00:00:53:42

The main challenge of this project was to bring

the smoke ventilation system

00:00:53:42 – 00:01:00:30

in three industrial halls into compliance,

while taking account of technical and budgetary constraints.

00:01:01:04 – 00:01:07:32

Before work began,

our teams carried out a full survey of the existing installations

00:01:08:04 – 00:01:14:46

to identify which equipment could be retained

and which needed to be replaced.

00:01:14:48 – 00:01:18:24

The aim is to optimise costs as much as possible

00:01:18:24 – 00:01:25:36

by reusing some equipment,

while ensuring the system is reliable and compliant.

00:01:26:46 – 00:01:32:32

For this project, some motors

that were still working in Hall 3

00:01:32:32 – 00:01:39:46

were removed and reused in Hall 2

to replace the motors that were not working.

00:01:41:32 – 00:01:47:30

This approach made it possible to make intelligent use of

part of the existing installations

Read the full transcriptCollapse transcript

00:01:47:30 – 00:01:53:05

to optimise costs,

while maintaining the system’s expected performance.

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeBuilding and site safety and security
  • SubjectNews
  • CompanyD+H BeLux
Share this article

Advertisement

Follow on Construire la Wallonie

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.